Acest laborator este dotat cu ultimele tehnici de masurare care permit incercarea transformatoarelor de putere, transformatoarelor de masura si a aparatajului de inalta tensiune, inclusiv incercari de tip si speciale in conformitate cu standardele internationale.

Din anul 1995, Laboratorul a fost acreditat de catre Asociatia de Acreditare din Romania – RENAR (membra a ILAC si EA) in conformitate cu IEC / ISO 17025.

Certificat RENAR

 

Echipamente de incercare

Generator de impuls 4,2 MV; 336 kWs

Incercarea la impuls
de tensiune de trasnet
4200 kV(336kWs)
700 kV (4,9kWs)
de comutatie
2600 kV
300 kV

 

 

 

Incercarea cu tensiune alternative aplicata

25 Hz to 150 Hz
1200 kV (hala)
1,2 A
1800 kV (aer liber)
1,2 A
50 Hz
200 kV
0,5 A
350 kV
0,75 A
3x250 kV
(sistem rezonant)
1 A

De la 25 Hz pana la 150 Hz trifazat

15 kV; 35 kV;110 kV
5 MVA
2 min

Incercarea la curent continuu
1100 kV
30 mA

 

 

Laboratorul de Incercari la Inalta Tensiune consta din:

- o camera de inalta tensiune ecranata (48 m x 32 m x 27 m) pentru incercarile speciale si de tip (cu generatorul de impuls de 4,2 MV, cascada de transformatoare de curent alternativ 1,2 MV si, redresorul de c.c in cascada de 1,1 MV, echipamentul de ploaie artificiala)
- camera de tensiune indusa (36 m x 32 m x 27 m) pentru testele de rutina
- camp de incercare in aer liber (30 m x 35 m) pentru incercarea de fiabilitate.

TEHNICI DE MASURARE

Sistem de masurare a tensiunilor inalte format din divizor de tensiune si voltmetru de varf

• Divizor de impuls de trasnet si de comutatie (643/4200 [pF] / [kV] (montat impreuna cu generatorul) conform cu IEC 60060-2/94), Amendament 1/96
Timp de raspuns – 10 ns

• Divizor de impuls de trasnet 10/2200 [kohm] / [kV]
Timp de raspuns – 27 ns

• Divizor de impuls de trasnet 10/770 [kohm] / [kV]
Timp de raspuns – 10 ns

• Divizor capacitiv de c.a. 160/1200 [pF] / [kV]
(montat impreuna cu cascada de c.a)

• Divizor capacitiv de c.a. 200/1800 [pF] / [kV]
(montat impreuna cu unitatea de cascada superioara din spatiul din aer liber)

• Sistem de masurare de referinta conform cu IEC 60-2 pentru LI(SI), tensiune de c.a, c.c si sarcina de impuls pentru masurari DP, avand trasabilitatea la PTB

• Echipament specializat pentru inregistrarea fenomenulor tranzitorii (inregistrari tranzitorii 10 biti, 100 MS/s, 3 canale)

• Echipament specializat pentru masurarea descarcarilor partiale prin metode electrice si ultrasonice, cu surse libere de DP pana la 500 kV

• Echipament de masurare a conditiilor atmosferice in timpul incercarilor IT

SERVICES OFFERED

High voltage tests for HV equipment
(transformers, cables, switchgears, GIS, etc.)
inside the electromagnetic screened hall of ICMET

High voltage tests on site:

- Full wave (1.2 / 50 s ) and tail chopped wave voltage impulse tests (between 2 and 8 s) at voltages up to 4200 kV and energy 336 kWs
- Applied voltage tests at frequencies between 25 and 150 Hz up to 800 kV
- Single and three-phase induced voltage test, 5 MVA, 2 min.
- DC voltage tests uo to 1200 kV 30 mA, up to 1200 kV
- Oscillating switching impulse tests
- Aperiodic switching impulse tests up to 2600 kV
- External insulation test under artificial rain for equipment up to 400 kV rated voltage
- Partial discharge and radio interference measurements
- Combined voltage tests: LI - AC, SI - AC, DC - LI, DC - SI

- AC sparkover voltage test of arresters up to 60 kV
- AC or DC voltage test of high voltage cables up to 100 kV
- AC voltage test of SF6 enclosed stations up to 250 kV (resonant equipment)
- Induced voltage test of distribution transformers
- Switching impulse test for instrument and power transformers by electromagnetic induction
- Partial discharge measurement at instrument and power transformers by electric and ultrasonic method.

 

The accredited tests for High Voltage Testing Laboratory

Test Type

The main test and / or measuring equipment

Tested item

The reference documents (norms)

1. Lightning impulse test (LI)
1.1 Lightning impulse test (LI) 1,2 / 50 µs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


1. Capacitive divider for LI 4.2MV
2. Resitive divider for LI 2,2MV,
10 kOhm
3.Damped capacitive divider 2MV
4.Haefely impulse oscilloscope
type 72E, with photographic device, maximum input signal 1500V,
with 9 steps, sweep base time (0,1¸ 500)m s/cm
5. AEG impulse oscilloscope type 018, with the photographic device, maximum input signal 700V.
6. Haefely peak voltmeter type 64 m, class ± 1%
7. Peak voltmeter type MUT-7,
class ± 1%
8. Impulse peak voltmeter type SMUT-1
9.GIT 700kV max.4,96kWs
10.GIT 4,2MV max.336kWs
11.Sphere gap f 1500mm, vertical position
12. Sphere gap 750mm, vertical position
13. Sphere gap f 250mm, horizontal position
14. Resistive divider for LI, 0,77MV/101 Ohm
15 Digital impulse measuring system for LI type TR-AS 100-10/3.

1.Oil-immersed power transformers up to 400MVA, 400kV class, inclusively

IEC 60-1/89 Sect.6
IEC 60-2/94, Sect.9

IEC 60076-3/2000
IEC 722/82

2.Dry power transformers up to 3000kVA, 36kV class, inclusively

IEC 60726/82

3.Current transformers up to 400kV class, inclusively

IEC 60185/1994
IEC 60044-1/96 9.1

4.Voltage transformers up to 400kV class, inclusively

IEC 60186+A1/96
IEC 60186/87 (capacitive)
IEC 60044-2/97 (inductive)

5. Alternating current disconnectors up to 400kV class, inclusively

EN 60129+A1/96
IEC 62271-100/2001
IEC 60071-1/96
IEC 60694/96

6. Alternating current circuit breakers up to 400kV class, inclusively

IEC 60071-1/96
IEC 60694/96
IEC 62271-102/2001

7.Enclosed busbars

IEC 60071-1/93
IEC 60071-2/96

8. Bushing

EN 60137/98
IEC 60137/95

9. AC metal-enclosed switchgear and controlgear for rated voltages, above 1kV and up to 72.5kV, inclusively(High-Voltage prefabricated substation).

IEC 60298/1999

10. Arrester

IEC 60099-1/94
IEC 60099-1/91

11.   a- Reactors

IEC 60289/88

b- Capacitors

IEC 60358/96
IEC 60358/90

c- Neutral resistances

SR 6669-2/86

12. High voltage fuses: current limiting fuses

IEC 60282/1-2002

1.2. Lightning impulse test with measurement of transferred over-voltage from the high-voltage winding to a low voltage winding.

GIT 4,2MV max:336 kWs or
low-voltage GIR
Capacitive divider 4,2MV
Resistive divider 770kV/ 10kOhm
Impulse cathodic oscilloscope or digital impulse measuring system type TR-AS 100-10/3.

1. Oil - immersed or dry power transformers up to 400MVA; 400kV class, inclusively.

IEC 60076-3/2000

2. Power - frequency voltage tests.
2.1. Separate - source voltage test (50Hz)

1.DC 1,2MV type WMC+WMUT-3
2.DC 600kV type MCF + WMUT-3
3.DC 350kV type MCF + MU9
4.DC 300kV type MCF+WMUT-3
5.Transformers cascade 1,5MVA; 1200kV
6.Test transformer 350kVA;350kV
7.Test transformer 200kVA; 200kV
8.HV source 1,5kVA; 10/0,22kV
9.Motor-generator group Smax=5MVA; Umax-12kV; f=(25¸ 150)Hz
10.Artificial rain plant
11.Check device of the second figure specific to protection degree
(3; 4 and 5).




1.Oil-immersed and dry power transformers up to 400MVA, 400kV class, inclusively

IEC 60-1/89, Sect.5
IEC 60-2/94, Sect.8

IEC 60076-3/2000
IEC 60726/82

2.Voltage transformers up to 400kV class, inclusively

IEC 60186+A1/96
IEC 60186/87 (capacitive)
IEC 60044-2/97 (inductive)

3. Current transformers up to 400kV class, inclusively

IEC 60185/1994
IEC 60044-1/96

4. Alternating current disconnectors up to 400kV class, inclusively, dry and wet conditions

EN 60129+A1/96
IEC 62271-100/2001
IEC 60071-1/96
IEC 60694/96

5. Alternating current circuit-brekers up to 400kV class, inclusively, dry and wet conditions

IEC 60071-1/96
IEC 60694/96
IEC 62271-102/2001

6. Enclosed busbars

IEC 71-1/93
IEC 71-2/96

7. Bushing, dry and wet conditions

EN 0137/98
IEC 60137/95

8. AC metal-enclosed switchgear and controlgear for rated voltage above 1kV and up to 72.5kV, inclusively (High-voltage prefabricate substation), dry and wet conditions.

IEC 60298/99

9. Arresters

IEC 60099-1/94

10.  a-Reactors

IEC 60289/88

b-Capacitors

IEC 60358/96

c-Neutral resistances

EN 60529/95

2.2. Induced over-voltage test (150Hz)

1.Motor-generator group Smax=5MVA; Umax=12kV; f=(25¸ 150)Hz
2.Induced voltage power station 15/35/110kV with following composition
a) 3MVA; 22,5(45)± 13x1,445%/6(12)kV power transformer
b) 500kVA; 6(12)/125(250)kV power transformer
c) 1000kVA; 7,5 ± 30%/1,5 (3)kV power transformer
d) TIRBO 20kV/0,1kV; TEMU 35kV/0,1kV; TEMU 110kV/0,1kV instrument transformers
3.DC 300kV type MCF+WMUT-3
4.DC 600kV type MCF+WMUT-3
5.700kV damped capacitive divider

1. Oil-immersed and dry power transformers up to 400MVA, 400kV class, inclusively

IEC 60076-3/2000
IEC 60726/82

2.3.Measurement of the harmonics of the no-load current

Motor-generator group S=5MVA; 6(12)kV; f=50Hz
Induced voltage power station 110/35/15kV
Wave analyzer Hewlett Packard
type 3581.A
Power Harmonics Analyzer
type Fluke-41

Oil-immersed and dry power transformers up to 400MVA; 400kV class, inclusively

IEC 61000-4-7/91

3. Switching impulse test (SI) 250/2500 µs




1.Capacitive divider 4.2MV
2.Universal RC divider 2MV
3.Resistive divider for LI 2.2MV, 10kOhm
4.Impulse oscilloscope Haefely tip 72E with photographic device, max input signal 1500V, with 9 steps, sweep base time (0,1¸ 500)m s /cm
5.Impulse oscilloscope AEG type 018, with photographic device, input signal max.700V
6. Haefely Peak voltmeter type 64m, clasa ± 1%
7. Peak voltmeter type WUT-7, clasa ± 1%
8.Peak voltmeter type SMUT-1
9.GIT 700kV max., 4,96kWs
10.GIT 4,2MV max., 336kWs
11.Digital impulse measuring system for SI type TR-AS 100-10/3
12. Sphere gap F 1500mm ,vertical position
13. Sphere gap F 750mm, vertical position
14.Sphere gap F 250mm, horizontal position




1.Power transformers up to 400 MVA, 400kV class, inclusively

IEC 60-1/89
IEC 60-2/94

IEC 60076-3/2000
IEC 60722/82

2.Instrument transformers up to 400kV class, inclusively
a-Current transformers


b-Voltage transformers




IEC 60185/94
IEC 60044-1/96
IEC 60186+A1/96
IEC 60186/87 (capacitive)
IEC 60044-2/97 (inductive)

3.Circuit-brekers up to 400kV class, inclusively

IEC 62271-102/2001

4.Current disconnectors up to 400kV class, inclusively

EN 60129+A1/96
IEC 62271-100/2001

4. Measurementr of capacity and tan delta

1.High voltage Schering bridge type SIEMENS
2.Standard capacitor 100pF; 100kV and 200kV
3. AC voltage sources from cr.no.2
4. Screens, flexible metalic tubs

1.Power transformers up to 400MVA, 400kV class, inclusively

SR 6669-1;3/86
SR 1703-7/80

2. Bushings up to 400kV class, inclusively

IEC 60137/95
EN 60137/98

3. Capacitors

IEC 60358/90

4.Instrument transformers

IEC 60185/94
IEC 60044-1/96
IEC 60186-1+A1/96
IEC 60186/87 (capacitive)
IEC 60044-2/97 (inductive)

5. Measurement of partial discharge level

1.Voltage sources from cr.no.2 or 3
2.Coupling capacitor Micafil 600kV
3.Partial discharge measuring instruments LMZ, AEG, MTE
4.Calibrating generator: RFT; PET-2
5.Frequency analyzer
6. Tektronix oscilloscope
type 2212, 60MHz
7.Ultrasonic detectors type DUDP


1.Power transformers up to 400MVA, 400kV class, inclusively

IEC 60-1,2/89;94
IEC 60076-3/2000
IEC 60270/2000

2. Instrument transformers up to 400kV, inclusively
a) Current transformers
b) Voltage transformers

IEC 60044-1/96
IEC 185/94
IEC 60270/2000
IEC 60044-2/97
IEC 60186/87
IEC 60186+A1/96

3. Bushings

IEC 60270/2000
IEC 60137/95
EN 60137/98

6. Measurement of RIV by conduction and radiation way

1.Voltage sources from crt.no.2 or 3
2.Coupling capacitor Micafil, 600kV
3.Measuring instruments of RIV; LMZ
4.Calibration generator: RFT
5.Frequency analyzer


1.Power transformers up to 400MVA, 400kV class, inclusively

IEC 60-1,2/89/94
NEMA TR 1/1974

2.High voltage equipment

IEC 60437/97
IEC 60694/96
IEC 62271-100/2001
IEC 62271-102/2001
CISPR 18-2/86
EN 60129+A1/96
EN 61284/2000

7. Direct current high voltage test up to Umax=1200kV

1.Cascade rectifier, Greinacher mounting circuit with Umax=1200kV; Imax=30mA
2.Resistive divider 1.2MV included in testing equipment

-Electric cables;
-Capacitors;
-Circuit-breakers;
-SF6 enclosed equipment;
-Protective rods;
-Insulating stairs.

IEC 60-1/89
IEC 60-2/94

8.Emission tests for EMC
8.1 Radio disturbance measurement by conduction at low voltage equipment

1.Artificial network SMZ 5; SMZ 6;
75 Ohm
2.Radio disturbance measuring instrument type SMV 6.1
-0.15-50 MHz;
-input impedance 50 Ohm; 75 Ohm
-artificial network NNB 103,
50 Ohm/50µH
3.TDS-524 oscilloscope
4.Radio disturbance measuring instrument type SMV 42/98
5.Artificial network 41/98

-Industrial equipment, scientific, medical and electric light equipment
-Equipment, systems used in power electronics
-Information technology equipment
-Household appliances electric tools

CISPR 16-1/1999
CISPR 16-2/1999+A1/99
SR EN 55011/1997
CISPR 14-1/2000
SR EN 55015/1995
CISPR 22/1997+A1/2000
8.2 Measurement of disturbance power by conduction for low voltage equipment 1.Interference electromagnetic
receiver SMV 42
2.Absorbing clamp
-Electric motor operated and thermal appliances for household and similar purposes;
-Electric tools;
-Motor-operated electro-medical apparatus;
-Electric toys running on tracks;
-Automatic goods dispensing machines and automatic entertaining machines
CISPR 14-1/2000
SE CISPR 16-1:1999
CISPR 16-2/1999+A1/99
8.3 Harmonic current emissions measurements for low voltage equipment 1.Harmonics analyzer and flicker
type HAR 1000-1P
2.IBM PC Computer
-Electrical and electronically equipment, including unprofessional arc welding equipment, with an input current less then
16A/ phases which are intended to be connected in low-voltage supply systems.
SR EN 61000-3-2:2001
CEI 61000-4-7:2002

8.4 Voltage fluctuations and flicker measurement for low voltage equipment 1.Harmonics analyzer and flicker
type HAR 1000-1P
2.IBM PC Computer
-Electrical and electronically equipment, intended to be use in 220 and 250 V, 50 Hz low voltage supply systems with ratted current less then 16 A/phase and up/subjected at special connection SR EN 61000-3-3:1998
CEI 61000-3-3:1994 +A1/2001

9.Direct current high voltage test up to Umax=1200kV

1.Cascade rectifier, Greinacher mounting circuit with Umax=1200kV;
I max=30mA

2.Resistive divider 1.2 MV included in testing equipment

-Electric cables;
-Capacitors;
-Circuit-breakers;
-SF6 enclosed equipment;
-Protective rods;
-Insulating stairs

STAS 6669/1;2;3-86
IEC 60-1/89
IEC 60-2/94

10.Combined voltage test
(LI or SI; AC; DC)
1.Impulse generator 4.2 MV + its own capacitive divider
2.Transformer cascade + its own capacitive divider
3.Cascade rectifier 1.2 MV + its own resistive divider
4.Separating capacitor Un=220kV mounted over an insulated platform for insulating level U=400kV
5.Insulated limiting resistance 17 kOhm
6.Sphere gaps, diameter 250mm, 500mm and 1500mm
7.Damped capacitive divider RC 1.5MV
8.Capacitive divider 350kV
9.Digital measuring system for LI, SI type TR-AS 100-10/3
-Electric equipment STAS 6669/1;2;3-86
IEC 60-1/89
IEC 60-2/94
IEC 60694/96
SR EN 60694+A1+A2/96

 


Responsabil incercari: Ing. Ion Badea
Telefon: 0351 404888; 0351 404889
FAX: 0351 404890
e-mail: ibadea@icmet.ro


Lista de referinte:

Download document


Lucrari publicate


Send mail to market@icmet.ro with questions or comments about this web site.
Copyright © National Institute for Research-Development and Testing in Electrical Engineering
ICMET-Craiova

Home
Back