List of calibrations according DKD accreditation

Measurand
Measuring range
Measuring conditions
Measuring uncertainty
Remarks
DC Low Voltage
350 mV to 1000 V
0,02%
Measuring Instruments
HV Measuring Systems
DC - Direct Current
DC High Voltage
25 kV to 350 kV
350 kV to 1000 kV
0,4%
1%
AC Low Voltage
1 V to 1000 V
10 Hz to 10 kHz
0,11%
Measuring Instruments
HV Measuring Systems
AC - Alternating Current
AC High Voltage
25 kV to 200 kV
200 kV to 1200 kV
50 Hz to 150 Hz
0,8%
1,0%

LV Impulse: LI
                  LIC
                  SI

500 V to 1000 V
50 V to 750 V
50 V to 1000 V

According IEC 1083
Load:
over 1MOhm,
less 50 pF

Coaxial cable
1,5 m length

0,6%
0,8%
0,6%
Measuring Instruments
LV - Low Voltage

Time parameters:
LI: T1
     T2
LIC: TC
SI: TP
     T2


0,84 µs
60 µs
0,5 µs
20 µs
4000 µs


2,0%
2,0%
2,0%
2,0%
2,0%
LV Impulse: LI


                  SI
180 kV to 210 kV
50 kV to 500 kV
500 kV to 180 kV
180 kV to 210 kV
50 kV to 500 kV
According IEC 60
0,6%
0,8%
0,8%
0,6%
0,8%
HV Measuring Systems
HV - High Voltage
LI - Lightning Impulse
LIC - Lightning Impulse Chopped
SI - Switching Impulse
T1 - Front time
T2 - Tail time
TC - Chopped time
TP - Peak time

Time parameters:
LI: T1
     T2
SI: TP
     T2

0,8 µs to 1,6 µs
40 µs to 60 µs
200 µs to 300 µs
1000 µs to 4000 µs

4%
4%
4%
4%

Impulse charge

Indication linearity

2 pC to 2000 pC

2 pC to 20 pC
20 pC to 2000 pC
According IEC 270
0,5 pC + 0,03q

0,05q
0,01q
PD Calibrators

PD Measuring Devices
PD Partial Discharge

 


High Voltage Calibration Laboratory DKD-K-18702
has the following reference measuring systems and standards:

Go top


List of the reference measuring systems and the reference calibrators
Go top
Measurand / measuring equipment Component elements Type Manufacturer
Direct Current (DC) High Voltage / Reference Measuring System Voltage Divider

Digital Voltmeter
HVD-200-1
Spellman Co.
Keithley 2000
Lightning Impulse (LI) and Switching Impulse (SI) High Volatge /
Reference Measuring System
Voltage Divider

Digital High Voltage Measuring System
SMCR 600/500
Highvolt Co.
TR-AS 100-10/3
Dr. Strauss Co.
Alternating Current (AC) High Voltage / Reference Measuring System Voltage Divider

Digital High Voltage Measuring System
SMCR 600/500
Highvolt Co.
TR-AS 100-10/3
Dr. Strauss Co.
LI and SI Low Voltage Impulse Charge / Reference Impulse Calibrator Calibrator KAL 1000
Dr. Strauss Co.
Impulse Charge / Reference Calibrator

Impulse Charge
Generator

LDC-5/R
Lemke
Diagnostics Co.
DC and AC Low Voltage / Reference Calibrator Calibrator 5500 A
Fluke


Pictures

 

   

Send mail to market@icmet.ro with questions or comments about this web site.
Copyright © 2003 Research-Development and Testing National Institute for Electrical Engineering